Environment |
| Ambient Operating Temperature |
0º to 40ºC 0º to 50ºC with derating |
| Cooling method |
Forced convection |
| Humidity |
95% maximum non-condensing at 40ºC |
| Storage Temperature |
-40º to 50ºC |
| Altitude |
0 to 3000m. Derate 1% per 100m between 1000m and
3000m |
| Vibration |
Tested in accordance with IEC 68-2-34 Mechanical
Shock In accordance with IEC 68-2-27 |
| Enclosure |
IP 20 (NEMA1), IP 54 (NEMA12) through panel
mounting |
| Electromagnetic Immunity |
In compliance with IEC801 and EN50082-2, and
complies with EN61800-3 with built-in filter |
| Electromagnetic Emissions |
In compliance with EN50081-2 when the recommended
RFI filter is used and EMC installation guidelines are followed |
| |
| |
AC Supply Requirements |
| Voltage |
|
200 to 240 VAC ±10%
380 to 480 VAC ±10%
500 to 575 VAC ±10%
500 to 690 VAC ±10% |
| Phase |
3Ø |
| Phase Imbalance Tolerance |
2% negative phase sequence (equivalent to 3%
voltage imbalance between phases) |
| Frequency |
48 to 65 Hz |
| Input Displacement Power Factor |
0.93
|
| |
| |
Control |
| Switching Frequency |
|
3, 4, 6, 8, 12, 16 kHz |
| Output Frequency |
0 to 3000 Hz (Open loop) |
| Output Speed |
0 to 40,000 rpm (Closed loop) |
| Frequency Accuracy |
±0.01% of full scale |
| Frequency Resolution |
0.001 Hz |
| Analog Input Resolution |
16 Bit + sign (Qty 1),10 Bit + sign (Qty 2) |
| Serial Communications |
2 or 4-wire RS232 or RS485. Protocol is ANSI x
3.28-2.5-A4, or Modbus RTU |
| Baud rate |
300 to 115,200 |
| Braking |
DC injection braking (stopping and holding)
standard. Dynamic braking transistor standard |
| Mains Dip Ride Through |
Up to 1 second depending on inertia and decel
time |
| |
| |
Protection |
| DC Bus Undervoltage Trip |
|
175 / 350 / 435 VDC
(approximately 124 / 247 / 307 VAC line voltage) |
| DC Bus Overvoltage Trip |
415 / 830 / 990 VDC
(approximately 293 / 587 / 700 VAC line voltage) |
| MOV Voltage |
160 Joules, 1400 VDC clamping |
| Transient Protection |
(Line to line and line to earth) Drive Overload
Trip Current overload value is exceeded. Programmable for Normal
Duty or Heavy Duty, Open loop or Closed loop operation |
Instantaneous
Overcurrent Trip |
225% of drive rated current Overcurrent Trip |
| Phase Loss Trip |
DC bus ripple threshold exceeded |
| Overtemperature Trips |
Drive heatsink, control board, and option
module(s) monitoring |
| Short Circuit Trip |
Protects against output phase to phase fault |
| Earth Fault Trip |
Protects against output phase to ground fault |
| Motor Thermal Trip |
Electronically protects the motor from
overheating due to loading conditions |
| |
| |
Approvals & Listings |
| UL, cUL |
|
Listed E171230 |
| IEC |
Meets IEC Vibration, Mechanical Shock and
Electromagnetic Immunity Standards |
| CE |
Designed for marketing |
| NEMA |
NEMA 1 enclosure type |
| VDE |
Meets VDE Electromagnetic Emissions Standards |
| ISO9001: 2000 |
Certified Manufacturing Facility |
| ISO 14001 |
Certified Manufacturing Facility |
| |